Back to the backflow review queue

Backflow assembly test: Crossroads Elementary School

Approved

Filed Sep 9, 2024 by Sam Brandt, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Sep 9, 2024
Assembly type
RP
Serial number
W477285
Size
4
Test gauge serial
G-2546
Gauge calibration date
Jun 21, 2024
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 001-14-01037
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6707 Quarry Rd
Owner: Ashby Holdings LLC
Parcel 001-14-01037