Backflow assembly test: Crossroads Elementary School
ApprovedFiled Oct 6, 2026 by Sam Brandt, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Oct 6, 2026
- Assembly type
- RP
- Serial number
- W477285
- Size
- 4
- Test gauge serial
- G-2809
- Gauge calibration date
- Mar 5, 2026
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Brandt, current on the service date
- All required fields present
- Address matches parcel 001-14-01037
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
6707 Quarry Rd
Owner: Ashby Holdings LLC
Parcel 001-14-01037