Back to the backflow review queue
Backflow assembly test: 6353 Hickory Trl
ApprovedFiled Jul 30, 2024 by Alex Benton, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 30, 2024
- Assembly type
- RP
- Serial number
- Z737012
- Size
- 3/4
- Test gauge serial
- G-5627
- Gauge calibration date
- Mar 16, 2024
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Benton, current on the service date
- All required fields present
- Address matches parcel 001-99-01251
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
6353 Hickory Trl
Owner: Shawn Kessler
Parcel 001-99-01251