Backflow assembly test: 9183 Orchard Ct

Approved

Filed Aug 13, 2025 by Reese Benton, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Aug 13, 2025
Assembly type
PVB
Serial number
W730274
Size
3/4
Test gauge serial
G-5311
Gauge calibration date
Oct 28, 2024
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Benton, current on the service date
  • All required fields present
  • Address matches parcel 009-66-01165
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9183 Orchard Ct
Owner: Morgan Danner
Parcel 009-66-01165