Back to the backflow review queue

Backflow assembly test: Corner Medical Offices

Approved

Filed Dec 30, 2025 by Blake Ellery, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Dec 30, 2025
Assembly type
RP
Serial number
W914916
Size
1
Test gauge serial
G-6338
Gauge calibration date
Jul 13, 2025
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Ellery, current on the service date
  • All required fields present
  • Address matches parcel 009-97-01137
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5073 Sycamore Way
Owner: Harlow Holdings LLC
Parcel 009-97-01137