Backflow assembly test: 4821 Ridgeview Way
ApprovedFiled Nov 8, 2024 by Rowan Marsh, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 8, 2024
- Assembly type
- PVB
- Serial number
- Z248122
- Size
- 1
- Test gauge serial
- G-4437
- Gauge calibration date
- Apr 7, 2024
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Marsh, current on the service date
- All required fields present
- Address matches parcel 009-94-01147
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4821 Ridgeview Way
Owner: Reese Okafor
Parcel 009-94-01147