Back to the backflow review queue
Backflow assembly test: 2143 Ridgeview Rd
ApprovedFiled Jul 12, 2025 by Blake Ellery, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 12, 2025
- Assembly type
- DC
- Serial number
- W835382
- Size
- 3/4
- Test gauge serial
- G-3795
- Gauge calibration date
- Jan 19, 2025
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Ellery, current on the service date
- All required fields present
- Address matches parcel 009-62-01108
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2143 Ridgeview Rd
Owner: Quinn Harlow
Parcel 009-62-01108