Backflow assembly test: Corner Pizza
ApprovedFiled Aug 20, 2026 by Rowan Marsh, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 20, 2026
- Assembly type
- DC
- Serial number
- A217048
- Size
- 1 1/2
- Test gauge serial
- G-6212
- Gauge calibration date
- May 21, 2026
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Marsh, current on the service date
- All required fields present
- Address matches parcel 009-23-01025
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4320 Orchard Ct
Owner: Fairley Holdings LLC
Parcel 009-23-01025