Backflow assembly test: 7664 Laurel Ct

Approved

Filed Feb 21, 2025 by Emerson Marsh, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Feb 21, 2025
Assembly type
RP
Serial number
W261665
Size
1
Test gauge serial
G-5584
Gauge calibration date
Sep 15, 2024
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Marsh, current on the service date
  • All required fields present
  • Address matches parcel 009-20-01160
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7664 Laurel Ct
Owner: Reese Benton
Parcel 009-20-01160