Back to the backflow review queue

Backflow assembly test: 8093 Cedar Hollow Ct

Approved

Filed May 2, 2026 by Avery Pruitt, Valley Backflow Testing. Filed from a phone.

Report

Date of service
May 2, 2026
Assembly type
DC
Serial number
W673570
Size
3/4
Test gauge serial
G-6993
Gauge calibration date
Feb 13, 2026
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 009-62-01313
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8093 Cedar Hollow Ct
Owner: Parker Kessler
Parcel 009-62-01313