Backflow assembly test: 4234 Turkey Hill Trl

Approved

Filed Nov 24, 2025 by Emerson Marsh, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 24, 2025
Assembly type
RP
Serial number
Z420702
Size
1
Test gauge serial
G-3805
Gauge calibration date
Oct 23, 2025
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Marsh, current on the service date
  • All required fields present
  • Address matches parcel 009-28-01180
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4234 Turkey Hill Trl
Owner: Sam Fairley
Parcel 009-28-01180