Backflow assembly test: Corner Medical Offices

Approved

Filed Nov 9, 2025 by Blake Ellery, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Nov 9, 2025
Assembly type
DC
Serial number
A589788
Size
1 1/2
Test gauge serial
G-6061
Gauge calibration date
Oct 8, 2025
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Ellery, current on the service date
  • All required fields present
  • Address matches parcel 009-58-01089
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6694 Mill Creek Ct
Owner: Calloway Holdings LLC
Parcel 009-58-01089