Back to the backflow review queue
Backflow assembly test: 3610 Meadow Lark Ln
ApprovedFiled Aug 12, 2025 by Parker Ashby, Northstar Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 12, 2025
- Assembly type
- DC
- Serial number
- W200043
- Size
- 3/4
- Test gauge serial
- G-7572
- Gauge calibration date
- May 24, 2025
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Ashby, current on the service date
- All required fields present
- Address matches parcel 013-93-01082
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3610 Meadow Lark Ln
Owner: Logan Lindqvist
Parcel 013-93-01082