Back to the backflow review queue

Backflow assembly test: 440 Ridgeview Ct

Approved

Filed Sep 23, 2026 by Morgan Ashby, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 23, 2026
Assembly type
PVB
Serial number
W921293
Size
3/4
Test gauge serial
G-6341
Gauge calibration date
Jul 28, 2026
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-54-01034
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

440 Ridgeview Ct
Owner: Jordan Harlow
Parcel 013-54-01034