Backflow assembly test: 4835 Pine Knoll Dr

Approved

Filed Aug 12, 2024 by Parker Ashby, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Aug 12, 2024
Assembly type
DC
Serial number
A176173
Size
1
Test gauge serial
G-7161
Gauge calibration date
Mar 31, 2024
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-11-01090
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4835 Pine Knoll Dr
Owner: Riley Calloway
Parcel 013-11-01090