Backflow assembly test: Station Bakery
ApprovedFiled Dec 29, 2023 by Casey Calloway, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Dec 29, 2023
- Assembly type
- DC
- Serial number
- A689124
- Size
- 4
- Test gauge serial
- G-6042
- Gauge calibration date
- Oct 19, 2023
- Check valve 1
- 4.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Calloway, current on the service date
- All required fields present
- Address matches parcel 013-31-01348
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.