Backflow assembly test: 9682 Ridgeview Ln
ApprovedFiled Feb 16, 2026 by Morgan Ashby, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 16, 2026
- Assembly type
- RP
- Serial number
- K722045
- Size
- 1
- Test gauge serial
- G-6468
- Gauge calibration date
- Jul 26, 2025
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Ashby, current on the service date
- All required fields present
- Address matches parcel 013-90-01094
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.