Back to the backflow review queue

Backflow assembly test: 3699 Turkey Hill Way

Approved

Filed Sep 27, 2026 by Morgan Ashby, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 27, 2026
Assembly type
RP
Serial number
W873499
Size
3/4
Test gauge serial
G-7114
Gauge calibration date
Apr 27, 2026
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-39-01246
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3699 Turkey Hill Way
Owner: Taylor Stroud
Parcel 013-39-01246