Back to the backflow review queue
Backflow assembly test: Main Street Self Storage
ApprovedFiled Dec 6, 2025 by Casey Benton, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 6, 2025
- Assembly type
- RP
- Serial number
- K564232
- Size
- 1
- Test gauge serial
- G-6980
- Gauge calibration date
- Jul 10, 2025
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Benton, current on the service date
- All required fields present
- Address matches parcel 013-58-01306
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6330 Hickory Ct
Owner: Ellery Holdings LLC
Parcel 013-58-01306