Back to the backflow review queue

Backflow assembly test: 7881 Sycamore Trl

Approved

Filed Sep 24, 2026 by Jamie Whitcomb, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Sep 24, 2026
Assembly type
DC
Serial number
B642937
Size
3/4
Test gauge serial
G-8922
Gauge calibration date
Aug 13, 2026
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 013-52-01215
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.