Backflow assembly test: Blue Heron Self Storage
ApprovedFiled Sep 23, 2025 by Casey Calloway, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 23, 2025
- Assembly type
- RP
- Serial number
- W845441
- Size
- 1 1/2
- Test gauge serial
- G-7533
- Gauge calibration date
- Jun 26, 2024
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 2.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Calloway, current on the service date
- All required fields present
- Address matches parcel 013-58-01324
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.