Backflow assembly test: 6219 Turkey Hill Trl
ApprovedFiled Jan 6, 2026 by Morgan Vance, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jan 6, 2026
- Assembly type
- RP
- Serial number
- A576243
- Size
- 3/4
- Test gauge serial
- G-6039
- Gauge calibration date
- Sep 3, 2025
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Vance, current on the service date
- All required fields present
- Address matches parcel 013-93-01144
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.