Backflow assembly test: 6235 Sycamore Trl
ApprovedFiled May 30, 2026 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 30, 2026
- Assembly type
- DC
- Serial number
- K667272
- Size
- 3/4
- Test gauge serial
- G-6503
- Gauge calibration date
- Sep 16, 2025
- Check valve 1
- 8.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Calloway, current on the service date
- All required fields present
- Address matches parcel 013-19-01020
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.