Back to the backflow review queue

Backflow assembly test: 8697 Laurel Ln

Approved

Filed Mar 19, 2024 by Blake Marsh, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Mar 19, 2024
Assembly type
RP
Serial number
B126517
Size
1
Test gauge serial
G-1617
Gauge calibration date
Feb 16, 2024
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Marsh, current on the service date
  • All required fields present
  • Address matches parcel 013-78-01295
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8697 Laurel Ln
Owner: Rowan Nguyen
Parcel 013-78-01295