Back to the backflow review queue

Backflow assembly test: 8697 Laurel Ln

Approved

Filed Mar 16, 2025 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 16, 2025
Assembly type
RP
Serial number
B126517
Size
1
Test gauge serial
G-6643
Gauge calibration date
Jun 9, 2024
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Calloway, current on the service date
  • All required fields present
  • Address matches parcel 013-78-01295
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8697 Laurel Ln
Owner: Rowan Nguyen
Parcel 013-78-01295