Back to the backflow review queue

Backflow assembly test: Crossroads Diner

Approved

Filed Aug 3, 2023 by Jamie Whitcomb, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Aug 3, 2023
Assembly type
RP
Serial number
B485202
Size
1 1/2
Test gauge serial
G-5153
Gauge calibration date
Apr 3, 2023
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 013-93-01033
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9138 Pine Knoll Way
Owner: Okafor Holdings LLC
Parcel 013-93-01033