Backflow assembly test: 9082 Meadow Lark Ln
ApprovedFiled Jul 7, 2025 by Blake Marsh, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 7, 2025
- Assembly type
- PVB
- Serial number
- A672094
- Size
- 3/4
- Test gauge serial
- G-9827
- Gauge calibration date
- Mar 29, 2024
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Marsh, current on the service date
- All required fields present
- Address matches parcel 013-62-01203
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9082 Meadow Lark Ln
Owner: Jamie Brandt
Parcel 013-62-01203