Back to the backflow review queue

Backflow assembly test: 6664 Fox Run Rd

Approved

Filed Sep 3, 2024 by Blake Marsh, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 3, 2024
Assembly type
RP
Serial number
B338788
Size
3/4
Test gauge serial
G-2316
Gauge calibration date
Jun 5, 2024
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Marsh, current on the service date
  • All required fields present
  • Address matches parcel 013-14-01315
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6664 Fox Run Rd
Owner: Blake Wexler
Parcel 013-14-01315