Backflow assembly test: 5333 Quarry Ct
ApprovedFiled Apr 9, 2026 by Morgan Ashby, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 9, 2026
- Assembly type
- DC
- Serial number
- W784697
- Size
- 3/4
- Test gauge serial
- G-5639
- Gauge calibration date
- Dec 29, 2025
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Ashby, current on the service date
- All required fields present
- Address matches parcel 013-98-01233
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.