Back to the backflow review queue
Backflow assembly test: 4530 Sycamore Trl
ApprovedFiled Mar 10, 2025 by Jamie Whitcomb, Northstar Backflow Testing. Filed from a phone.
Report
- Date of service
- Mar 10, 2025
- Assembly type
- RP
- Serial number
- Z277043
- Size
- 1
- Test gauge serial
- G-1224
- Gauge calibration date
- Aug 5, 2024
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jamie Whitcomb, current on the service date
- All required fields present
- Address matches parcel 013-13-01297
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4530 Sycamore Trl
Owner: Morgan Okafor
Parcel 013-13-01297