Backflow assembly test: 4530 Sycamore Trl
ApprovedFiled Feb 19, 2026 by Drew Ramirez, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 19, 2026
- Assembly type
- RP
- Serial number
- Z277043
- Size
- 1
- Test gauge serial
- G-8125
- Gauge calibration date
- May 17, 2025
- Check valve 1
- 5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Ramirez, current on the service date
- All required fields present
- Address matches parcel 013-13-01297
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.