Backflow assembly test: Station Animal Hospital

Approved

Filed Dec 18, 2025 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 18, 2025
Assembly type
RP
Serial number
K738467
Size
1
Test gauge serial
G-8862
Gauge calibration date
Feb 14, 2025
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
2.4 psid
Relief valve opened at
2.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Calloway, current on the service date
  • All required fields present
  • Address matches parcel 013-53-01255
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4522 Pine Knoll Rd
Owner: Wexler Holdings LLC
Parcel 013-53-01255