Backflow assembly test: Corner Market

Approved

Filed Aug 31, 2026 by Parker Ashby, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Aug 31, 2026
Assembly type
RP
Serial number
K452017
Size
1
Test gauge serial
G-5794
Gauge calibration date
Mar 29, 2026
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-21-01223
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.