Backflow assembly test: Hilltop Apartments

Approved

Filed Oct 9, 2025 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 9, 2025
Assembly type
DC
Serial number
K157361
Size
4
Test gauge serial
G-1058
Gauge calibration date
Aug 3, 2024
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Calloway, current on the service date
  • All required fields present
  • Address matches parcel 013-74-01150
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4188 Orchard Rd
Owner: Okafor Holdings LLC
Parcel 013-74-01150