Back to the backflow review queue

Backflow assembly test: 5299 Hickory Dr

Approved

Filed Jul 27, 2026 by Drew Ramirez, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 27, 2026
Assembly type
PVB
Serial number
W447689
Size
3/4
Test gauge serial
G-7490
Gauge calibration date
Nov 16, 2025
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
2.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 013-99-01109
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5299 Hickory Dr
Owner: Hayden Pruitt
Parcel 013-99-01109