Backflow assembly test: Station Brewing Co
ApprovedFiled Jun 7, 2025 by Parker Stroud, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 7, 2025
- Assembly type
- DC
- Serial number
- A906881
- Size
- 1
- Test gauge serial
- G-5972
- Gauge calibration date
- Oct 30, 2024
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Stroud, current on the service date
- All required fields present
- Address matches parcel 017-79-01173
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
9522 Orchard Ln
Owner: Nguyen Holdings LLC
Parcel 017-79-01173