Back to the backflow review queue

Backflow assembly test: 4052 Hickory Trl

Approved

Filed Dec 27, 2023 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Dec 27, 2023
Assembly type
RP
Serial number
A531009
Size
1
Test gauge serial
G-4113
Gauge calibration date
Sep 15, 2023
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-89-01073
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4052 Hickory Trl
Owner: Reese Brandt
Parcel 017-89-01073