Backflow assembly test: 4915 Hickory Ct
ApprovedFiled Aug 7, 2024 by Parker Stroud, Valley Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 7, 2024
- Assembly type
- RP
- Serial number
- W280999
- Size
- 1
- Test gauge serial
- G-3836
- Gauge calibration date
- Aug 6, 2023
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 1.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Stroud, current on the service date
- All required fields present
- Address matches parcel 017-83-01094
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4915 Hickory Ct
Owner: Casey Nguyen
Parcel 017-83-01094