Back to the backflow review queue

Backflow assembly test: 4915 Hickory Ct

Approved

Filed Jul 31, 2025 by Riley Brandt, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 31, 2025
Assembly type
RP
Serial number
W280999
Size
1
Test gauge serial
G-7393
Gauge calibration date
Feb 3, 2025
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Brandt, current on the service date
  • All required fields present
  • Address matches parcel 017-83-01094
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4915 Hickory Ct
Owner: Casey Nguyen
Parcel 017-83-01094