Backflow assembly test: Station Grill

Approved

Filed Nov 12, 2026 by Parker Stroud, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Nov 12, 2026
Assembly type
RP
Serial number
W220557
Size
1 1/2
Test gauge serial
G-3552
Gauge calibration date
Jul 3, 2026
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Stroud, current on the service date
  • All required fields present
  • Address matches parcel 017-86-01053
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3634 Pine Knoll Ct
Owner: Fairley Holdings LLC
Parcel 017-86-01053