Back to the backflow review queue

Backflow assembly test: 6681 Pine Knoll Rd

Approved

Filed May 2, 2024 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
May 2, 2024
Assembly type
RP
Serial number
K127306
Size
3/4
Test gauge serial
G-2507
Gauge calibration date
Jul 25, 2023
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-66-01201
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6681 Pine Knoll Rd
Owner: Taylor Harlow
Parcel 017-66-01201