Back to the backflow review queue

Backflow assembly test: 6735 Mill Creek Rd

Approved

Filed Apr 26, 2024 by Riley Marsh, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 26, 2024
Assembly type
RP
Serial number
A613563
Size
1
Test gauge serial
G-6181
Gauge calibration date
Jul 16, 2023
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Marsh, current on the service date
  • All required fields present
  • Address matches parcel 017-38-01063
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6735 Mill Creek Rd
Owner: Shawn Calloway
Parcel 017-38-01063