Back to the backflow review queue

Backflow assembly test: 6735 Mill Creek Rd

Approved

Filed Apr 25, 2025 by Parker Stroud, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Apr 25, 2025
Assembly type
RP
Serial number
A613563
Size
1
Test gauge serial
G-4504
Gauge calibration date
Aug 23, 2024
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Stroud, current on the service date
  • All required fields present
  • Address matches parcel 017-38-01063
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6735 Mill Creek Rd
Owner: Shawn Calloway
Parcel 017-38-01063