Backflow assembly test: 2885 Quarry Way
ApprovedFiled Oct 20, 2024 by Riley Marsh, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 20, 2024
- Assembly type
- DC
- Serial number
- A241312
- Size
- 3/4
- Test gauge serial
- G-8142
- Gauge calibration date
- Oct 13, 2023
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Marsh, current on the service date
- All required fields present
- Address matches parcel 017-70-01077
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.