Backflow assembly test: Riverside Grill

Approved

Filed Aug 20, 2025 by Riley Brandt, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 20, 2025
Assembly type
DC
Serial number
B300523
Size
1 1/2
Test gauge serial
G-8998
Gauge calibration date
Mar 30, 2025
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Brandt, current on the service date
  • All required fields present
  • Address matches parcel 017-29-01042
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6758 Cedar Hollow Ln
Owner: Brandt Holdings LLC
Parcel 017-29-01042