Backflow assembly test: Two Rivers Self Storage

Approved

Filed May 6, 2025 by Parker Stroud, Valley Backflow Testing. Filed from a phone.

Report

Date of service
May 6, 2025
Assembly type
RP
Serial number
W600665
Size
2
Test gauge serial
G-7325
Gauge calibration date
Oct 31, 2024
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Stroud, current on the service date
  • All required fields present
  • Address matches parcel 017-76-01185
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3889 Laurel Ct
Owner: Danner Holdings LLC
Parcel 017-76-01185