Backflow assembly test: Two Rivers Market
ApprovedFiled Oct 30, 2025 by Avery Wexler, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Oct 30, 2025
- Assembly type
- RP
- Serial number
- W620499
- Size
- 1
- Test gauge serial
- G-1626
- Gauge calibration date
- May 4, 2025
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 1.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Wexler, current on the service date
- All required fields present
- Address matches parcel 017-35-01346
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.