Backflow assembly test: Two Rivers Market
Needs reviewFiled Nov 21, 2026 by Logan Fairley, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 21, 2026
- Assembly type
- RP
- Serial number
- W620499
- Size
- 1
- Test gauge serial
- G-6741
- Gauge calibration date
- Jun 18, 2026
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Fairley, current on the service date
- All required fields present
- Address matches parcel 017-35-01346
- Readings in range, no flags
- Result: passing. Next due date resets when approved.