Back to the backflow review queue
Backflow assembly test: 2057 Ridgeview Trl
ApprovedFiled Jun 22, 2026 by Logan Fairley, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 22, 2026
- Assembly type
- RP
- Serial number
- Z900456
- Size
- 1
- Test gauge serial
- G-3433
- Gauge calibration date
- Feb 23, 2025
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Fairley, current on the service date
- All required fields present
- Address matches parcel 017-26-01106
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2057 Ridgeview Trl
Owner: Parker Ashby
Parcel 017-26-01106