Backflow assembly test: 1998 Orchard Dr

Approved

Filed Dec 5, 2024 by Avery Wexler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Dec 5, 2024
Assembly type
RP
Serial number
K586540
Size
1
Test gauge serial
G-7066
Gauge calibration date
Sep 11, 2024
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Wexler, current on the service date
  • All required fields present
  • Address matches parcel 017-40-01211
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.